The UL flame exposure is a vertical-tray fire test for determining values of cable damage height and smoke release from electrical and optical-fiber cables when the cables are subjected to a flaming ignition source. For a cable to be acceptable under the UL test procedure, each of the following is to be exhibited (see 10.1 and 10.2):
a) The cable char height is to be less than 8 ft, 0 inch (244 cm) when measured from the bottom of the cable tray in accordance with Section 8.
b) The total smoke released is to be 95 m2 or less.
c) The peak smoke release rate is to be 0.25 m2/s or less.
更多关于UL 1685测试,请咨询泰思泰克
咨询电话:(86)0512-66315780,(86)0512-66315430
网址:www.testech.com.cn
邮箱:sales01@testech.com.cn info@testech.com.cn